WHERE THESE PUMPS RUN
FAMILIAR PUMPS, A MUCH HARDER DUTY CYCLE.
Pump designs common in commercial buildings and process plants now run in data centers, hospitals and fabs, where a single failure can take cooling capacity offline and wasted energy counts against efficiency targets.
Chilled-water circulation | Condenser water | Cooling-tower transfer | Liquid-cooling loops | Fire protection & booster
WHERE PUMP BEARINGS FAIL
PUMP BEARINGS RARELY FAIL FROM FATIGUE.
They fail from the conditions around them. These four show up most in continuous-duty pumps.
01
Changing thrust loads
Variable-speed operation moves pumps away from their best efficiency point, changing the size and sometimes the direction of hydraulic thrust. Very light axial loads can let balls skid in angular contact bearings.
We recommend:
Matched pairs of 40° angular contact ball bearings, selected and preloaded for the full operating range.
02
MOISTURE IN THE LUBRICANT
Chilled-water pumps run cold. Humid air drawn into the bearing housing condenses, and water in the oil or grease shortens bearing life.
We recommend:
Sealed deep groove ball bearings, corrosion-resistant options and guidance on housing sealing.
03
ELECTRICAL EROSION
VFD-driven motors can pass shaft current through the bearings of close-coupled pumps, fluting the raceways and causing noise and early failure.
We recommend:
Insulated hybrid ceramic bearings that break the current path.
04
STANDBY PUMPS THAT SIT STILL
Redundant (N+1) systems keep pumps idle beside running ones. Vibration from neighboring equipment can mark the raceways of a stationary bearing, known as false brinelling.
We recommend:
Bearing and lubricant selection for standby duty, plus guidance on rotation schedules.
KOYO® BEARINGS FOR PUMPS
THE RIGHT BEARINGS FOR EACH POSITION AND DUTY.
Every bearing choice is also an efficiency decision. Low-friction designs and the right lubrication cut losses in pumps that run 8,760 hours a year.
FULL KOYO CATALOG
RADIAL POSITION
DEEP GROOVE BALL BEARINGS
The workhorse of the radial position. Sealed versions keep moisture out and grease in for close-coupled and smaller pumps.
THRUST POSITION
SINGLE-ROW ANGULAR CONTACT BALL BEARINGS, 40°
Supplied as matched pairs for high thrust loads in either direction, the standard choice for the outboard position.
THRUST POSITION
DOUBLE-ROW ANGULAR CONTACT BEARINGS
Two rows in one compact unit for combined radial and axial loads where frame space is tight.
RADIAL POSITION · LARGE PUMPS
CYLINDRICAL ROLLER BEARINGS
High radial load capacity for split-case and large end-suction pumps, with separable rings for easier assembly.
EXSEV · VFD-DRIVEN PUMPS
3NC HYBRID CERAMIC BEARINGS
Ceramic rolling elements block shaft current and run cooler at speed, protecting close-coupled pumps on variable-speed drives.
IN DATA CENTERS
COOLING UPTIME STARTS WITH THE PUMPS.
Chilled-water, condenser and liquid-cooling pumps carry the heat out of every data hall. When one fails, redundancy shrinks and cooling capacity is at risk. That is why data center owners now write reliability and efficiency requirements into pump specifications, and those requirements extend to the bearings.
ALL MISSION-CRITICAL EQUIPMENT
FOR DATA CENTER OPERATORS
DESIGNING A PUMP FOR CONTINUOUS DUTY?
Share the speed, loads and operating profile. A JTEKT applications engineer will review the bearing selection and provide recommendations.