WHY IT MATTERS IN 24/7 FACILITIES
THE LAST LINE OF DEFENSE.
Hospitals and data centers must have backup power at full load within seconds of an outage. Data centers back each utility feed with N+1 or 2N generator capacity, and some sites now run gas engines or turbines as continuous on-site prime power. Either way, the generator is only as dependable as the rotating parts inside it.
10 SECONDS
Maximum time to restore power to hospital life-safety and critical loads (NFPA 110 Type 10, required by NFPA 99).
96 HOURS
Typical minimum run-time class for hospital emergency power systems, or an operational plan to supply that much fuel.
Sources: NFPA 110, Standard for Emergency and Standby Power Systems; NFPA 99, Health Care Facilities Code; as summarized in Consulting-Specifying Engineer, “Hospital emergency power supply systems.”
OPERATING CHALLENGES
TWO DUTY PROFILES, BOTH HARD ON BEARINGS.
Standby sets fail from sitting still; prime-power sets wear from never stopping. These are the conditions that shorten generator bearing life.
01 · STANDBY
Long idle, then full load
Lubricant settles, moisture causes corrosion and nearby vibration marks stationary raceways (false brinelling), all before a start at full load.
02 · STANDBY
Short test runs
Monthly exercise runs rarely bring bearings up to operating temperature, so condensation and settled grease are never fully cleared.
03 · BOTH
Engine heat and vibration
Accessories mounted on the engine run hot and absorb firing-frequency vibration, which shortens grease life and loosens fits.
04 · BOTH
Shaft currents in the alternator
Voltage on the alternator shaft can discharge through the bearings, causing pitting and fluting. Inverter-fed fan and start motors add the same risk.
05 · PRIME POWER
Continuous duty
Behind-the-meter and prime-power plants run around the clock, so bearing life is measured in tens of thousands of hours between overhauls.
KOYO® TECHNOLOGIES THAT EXTEND LIFE
BUILT FOR THE IDLE AND THE RUN.
40%
3NC HYBRID CERAMIC BEARINGS
Silicon nitride balls insulate against shaft currents in alternators and inverter-fed motors. Operating temperature up to 40% lower than steel, for longer grease life.
2RD
RD LIGHT CONTACT SEAL
Starting torque close to a non-contact seal, with better water and dust protection than full-contact seals. Keeps grease in and moisture out while a set stands idle.
+15%
RSH2 HIGH CAPACITY
Larger balls add 15% load capacity without changing boundary dimensions, and a special heat treatment raises surface hardness for longer life.
VALVE TRAIN · HEAVY RADIAL LOAD
HJ SERIES NEEDLE ROLLER BEARINGS
Inch-series heavy-duty needle roller bearings with a machined outer ring and caged rollers. Run directly on a hardened shaft or pin, or with a matching inner ring, for high radial capacity in a compact section. Suited to roller followers, rocker shafts and accessory drives.
FOLLOWERS · FUEL SYSTEM · DRIVES
PRECISION PINS, ROLLERS AND SHAFTS
Custom components made in-house from machining through heat treatment and grinding, with diameter tolerances to 0.001 mm. Used in follower pins and rollers, diesel and gas fuel system parts and gear shafts.
COOLANT & WATER PUMPS
DOUBLE-ROW ANGULAR CONTACT BALL BEARINGS (DAC)
Two rows of balls in one unit carry combined radial and axial loads from pump impellers and belt drives, in less axial space than a pair of single-row bearings.
PROOF
EXPERIENCE IN GENERATOR BEARINGS.
Koyo developed and installed the first insulated hybrid ceramic bearings in wind turbine generators, one of the most demanding environments for shaft current. Koyo has supplied bearings to North American electric motor manufacturers and the motor repair market since 1958.
SERVICE & SUPPORT
ENGINEERING BEHIND EVERY BEARING.
- Application engineering Bearing selection and life review for new alternator and genset designs.
- Field service On-site support for installation and troubleshooting.
- Failure analysis Root-cause review of returned bearings, including electrical damage.
- Maintenance training Storage, mounting and lubrication practices for maintenance teams.
RUN OR MAINTAIN A FACILITY? FOR OPERATORS
APPLICATION ENGINEERING SUPPORT
JTEKT applications engineers review bearing selections for alternators and genset auxiliaries against actual duty, from long standby to continuous prime power.